Medium-voltage equipment

AT27-1-3
1234

Triol AT27 VFD, 6 kV, maximum output voltage 3-6 kV, cabinet-type

Triol АТ27-6kV cabinet-type variable-frequency drive is designed to control cage asynchronous and synchronous motors as well as synchronous motors with external exciter. Compact and ergonomic design provides an opportunity to comfortably adapt the product to the service conditions prevailing at a particular Customer’s facility. Triol AT27 control system makes it possible to readily integrate a variable-frequency drive into the manufacturing process. Triol IDrive technology used therein opens up new opportunities associated with remote control and adjustment.

  • Single side maintenance reduces installation size.
  • Enhanced personnel safety due to mechanical and electrical blocking systems that exclude the possibility of electrical shock during operation or service of the drive.
  • High overload capability – 120 % in 120 s.
  • Has a variety of protection functions of the drive, the motor and the mechanical load.
  • Increased reliability due to the use of 6 power cells for each phase and cell bypass function.
  • Low harmonic distortion of the supply (THDi)
  • Inverter efficiency higher than 98 %, transformer efficiency higher than 98 % (for power higher than 1600 kW).
  • Optional operation only from medium voltage supply voltage, without the need for external low voltage supply.
  • V/F, speed or torque control options.
  • Cascade control of several motors.
Rated supply voltage3 x 6 kV ± 15 %
Rated supply frequency50 Hz ±10 %
Overload capacityFor 60 sec — 120 %
For 3 sec — 150 %
For 10 ms — 200 %
Output frequency0 … 120 Hz ± 0.1%
Efficiency, not less than98 %
Power factor, not less than95
Number of phases3
Station auxiliaries voltage380 V
Average time between failures20 000 h
Coolingforced air cooling
Operation modecontinuous
Protection levelIP30
Working temperature-1…+40 ºС
Altitude characteristicsto 1000 m
StandardsGOST17516.1-90

 

Models of Triol AT27Rated motor power, kWRated output voltage
U = 6000 V/
Rated current of power circuit, A
Number of power cells per phase
АТ27-М20200256
АТ27-М25250306
АТ27-М32315406
АТ27-М40400506
АТ27-М50500606
АТ27-М63630756
АТ27-М80800956
АТ27-1М010001256
АТ27-1М212501556
АТ27-1М414001706
АТ27-1М616001956
АТ27-2М020002456
АТ27-2М525003056
АТ27-3М030003756
АТ27-3М232004006
АТ27-3М535004406
АТ27-4М040005006
АТ27-4М545005656
АТ27-5М050006256
АТ27-5М555006906
АТ27-6М363007906
АТ27-8М0800010156
АТ27-9М3930011806
АТ27-10М1050013306
АТ27-12М51250015856