Low-voltage equipment

AT24-line-b
123456

Triol AT24, Line B (HVAC) application, 380 V/480 V/660 V/690 V

Triol AT24 VFD Line 4 is known for its multifunctional performance and flexibility in such spheres of application as ventilation and air conditioning. Due to its optimal construction this VFD allows realization of a big variety of tasks. This makes the VFD universal solution. This line can be identified by high quality, easiness of access and simplicity of operation

  • Overload capacity is 120 % from the nominal during 60 sec;
  • Close-loop speed or torque control;
  • Open-loop speed or torque control;
  • EMC filter C2 category;
  • Possibility of installation in the rooms with the permanent presence of the staff;
  • Working temperature from -20 … +50 °C;
  • Analog sensors and PTC thermocouples support;
  • User-friendly removable control panel;
  • Control of the motors with permanent magnets;
  • Special algorithms of the pumps, compressors and fans;
  • Special HVAC functions (motor drying, energy savings calculation).
Supply voltage3х380 (-15 % .. +10 %)
Supply frequency50 Hz (-15 % .. +10 %)
EnclosureMetal
Degree of protectionIP54
EMC filterBuilt-in
DC reactorBuilt-in
Control panelGraphic, 160X160 pixels, 3’’
Braking resistorExternal
PWM frequency / PWM carrier frequency2 — 10 kHz/5 kHz
Output frequency0 — 400 kHz
Frequency range for the different motors0 — 400 kHz
Discrete change of frequency assignments0.1 Hz
Power factor> 0,95
Eefficiency96…97
Ccontrol laws• linear dependence U/f
• quadratic dependence U/f
• the programmable U/f
Ccurrent LimitMotoring and regenerative
Permissible cable length to the engineMax 30 m (screened)/ max 50 m (unshielded)
Braking• DC braking
• combined braking
Speed range• 1:1000 in a closed-loop system with a speed sensor
• 1:100 in an open-loop system
Speed accuracy (static)• ± 0,01 % in a closed-loop system
• ± 0.5 % in an open-loop system
Torque accuracy• ± 5 % in a closed-loop system
• ± 10 % in an open-loop system
Overload characteristics150 % for 2 seconds, 120 % for 60 seconds with an ambient temperature 50 °С
Asynchronous motor control profile• Vector control in a closed-loop system with a speed feedback;
• Vector control in open-loop system without a speed feedback;
• Voltage / frequency U / F ratio control (scalar control);
Cycle adjusmentPID-controller
Slip compensationImplemented
Local signalingOperation, ready, fault – green, yellow and red LEDs
Supply10 В DC, +/- 2 % current not exceeding 30 mA, 24 V, 300 mA
Number of analog inputs2
Analog input typeprogrammable 4..20 mA, 0..5 mA, 0..10 V
sampling period4 msec
Number of analog outputs1
Type Analog Outputprogrammable 4..20 mA, 0..5 mA, 0..10 V
Number of digital outputs4 relay outputs
Type of digital output• 2 switching types
• 2 normally open type
Number of digital inputs8
Type of binary input• 24 V, input resistance: ~ 4 kOhm
• RТС sensor
• Resistance switch 3 kOhm/1,8 kOhm
• emergency Stop
The logic of the digital input2 digital inputs arbitrary polarity
Acceleration and decelerationS-shaped acceleration / deceleration, linear adjustable
Type of protection• Power switch (U, V, W, T)
• Ud max/ Ud min
• Temperature keys
• Loss of one or more phases
• Overheating of the braking resistor
• Motor overload /motor overheating
Dielectric strengthfor power circuits and auxiliary circuits having electrical communication with the power circuit – 2500 V
Insulation resistance> 1 MOhm
Output frequency discreteness0.1 Hz
Communication protocolModbus
Physical interface2-wire RS-48S for Modbus
FrameservingRTU for Modbus
Data transfer rate• 115200 bps
• 1200-250000 bps
• up to 1 Mbps
Data format8 bit 1 stop bit, no parity
Addresses number1..255 of adresses for Modbus
Access methodSlave
Control optionsBluetooth module or Wi-Fi module
Electromagnetic compatibilityEN 55011 class A. group 2. IEC / EN 61800-3. category СЗ with the additional EMC filter. EN 55011 class В, group 1. IEC/EN 61800-3, category С1.
Relative humidity95 %
The ambient temperature during operation / storage-20 .. +50 °C / -40 .. +50 °C
Oerating altitudeto 1000 m
Standards• EN 61800-3:2004,
• EN 55011,
• EN 61000-6 ¾ ,
• GOST 24607-88.
• GOST 13109-97,
• GOST 15150-69,
• GOST 14254- 96,
• GOST 17516.1-90,
• GOST 12.1.044-89.
Triol AТ24 modelRated motor power, kWRated current of power circuit, ATotal output power of tde inverter, kVA
5К55.5117.5
7К57.51510
11К11.02215
15К15.03018
18К18.03622
22К22.04528
30К30.06038
37К37.07545
45К45.09056
55К55.011072
75К75.0150100
90К90.0180125
М11110.0220145
М13130.0260175
М16160.0320210
М20200.0400260
М25250.0500330
М32320.0640400
М40400.0800500