Low-voltage equipment

Triol AT24 37K line C
123456

Triol AT24, Line 1 (Lift, Elevator) application, 380 V/480 V/660 V/690 V

Triol AT24 VFD Line 4 is known for its multifunctional performance and flexibility in such spheres of application as ventilation and air conditioning. Due to its optimal construction this VFD allows realization of a big variety of tasks. This makes the VFD universal solution. This line can be identified by high quality, easiness of access and simplicity of operation.

  • High overload capacity — 220 % during 1 — 2 sec, 150 %during 60 sec;
  • Close-loop speed or torque control;
  • Open-loop speed or torque control;
  • Unique algorithms for hoists control;
  • EMC filter C2 category allows to install the equipment in the electrical room close to the testing and automation facilities;
  • Easy installation at the control cabinet;
  • Support of the absolute and incremental encoders;
  • Compatibility with the lift application VFD’s of the main manufacturers;
  • Measuring motor parameters at stand still (no shaft rotation);
  • Integrated braking chopper.
Supply voltage3х380 (-15 % .. +10 %)
Supply frequency50 Hz (-15 % .. +10 %)
EnclosurePlastic
Degree of protectionIP20
EMC filterBuilt-in
DC reactorBuilt-in
Control panelGraphic, 160X160 pixels, 3’’
Braking resistorExternal
PWM frequency / PWM carrier frequency2 — 10 kHz/5 kHz
Output frequency0 — 400 kHz
Frequency range for the different motors0 — 400 kHz
Speed range• 1:1000 in a closed-loop system with a speed sensor
• 1:100 in an open-loop system
Speed accuracy (static)• ± 0,01 % in a closed-loop system
• ± 0.5 % in an open-loop system
Torque accuracy• ± 5 % in a closed-loop system
• ± 10 % in an open-loop system
Overload characteristics220 % for 2 seconds, 150 % for 60 seconds with an ambient temperature 50 °С
Asynchronous motor control profile• Vector control in a closed-loop system with a speed feedback;
• Vector control in open-loop system without a speed feedback;
• Voltage / frequency U / F ratio control (scalar control);
Cycle adjusmentSetting the operating mode — MODBUS, digital inputs
Slip compensationImplemented
Local signalingOperation, ready, fault – green, yellow and red LEDs
Insulation• Isolated control circuit
• Insulated custom circuit
Supply10 В DC, +/- 2 % current not exceeding 30 mA, 24 V, 300 mA
Number of analog inputs2
Analog input typeProgrammable 4..20 mA, 0..5 mA, 0..10 V
Sampling period4 msec
Number of analog outputs1
Type analog outputProgrammable 4..20 mA, 0..5 mA, 0..10 V
Number of digital outputs4 relay outputs
Type of digital output• 2 switching types
• 2 normally open type
Number of digital inputs8
Type of binary input• 24 V, input resistance: ~ 4 kOhm
• RТС sensor
• Resistance switch 3 kOhm/1,8 kOhm
• emergency Stop
The logic of the digital input2 digital inputs arbitrary polarity
Acceleration and decelerationS-shaped acceleration / deceleration, linear adjustable
Type of protection• power switch (U, V, W, T)
• Ud max/ Ud min
• temperature keys
• Loss of one or more phases
• Overheating of the braking resistor
• Motor overload /motor overheating
Dielectric strengthFor power circuits and auxiliary circuits having electrical communication with the power circuit – 2500 V
Insulation resistance> 1 MOhm
Output frequency discreteness0,1 Hz
Communication protocolModbus
Physical interface2-wire RS-48S for Modbus
FrameservingRTU for Modbus
Data transfer rate• 115200 bps
• 1200-250000 bps
• up to 1 Mbps
Data format8 bit 1 stop bit, no parity
Addresses number1..255 of adresses for Modbus
Access methodslave
Control optionsBluetooth module or Wi-Fi module
Electromagnetic compatibilityEN 55011 class A. group 2. IEC / EN 61800-3. category СЗ with the additional EMC filter. EN 55011 class В, group 1. IEC/EN 61800-3, category С1.
Relative humidity95 %
The ambient temperature during operation / storage-20 .. +50 °C / -30 .. +80 °C
Operating altitudeto 1000 m
Standards• EN 61800-3:2004,
• EN 55011,
• EN 61000-6 ¾ ,
• GOST 24607-88.
• GOST 13109-97,
• GOST 15150-69,
• GOST 14254- 96,
• GOST 17516.1-90,
• GOST 12.1.044-89.
Triol AТ24 modelRated motor power, kWRated current of power circuit, ATotal output power of tde inverter, kVA
5К55,5117,5
7К57,51510
11К11,02215
15К15,03018
18К18,03622
22К22,04528
30К30.06038
37К377545